Enquire For Price
Delivery & Shipping
GO Fire Rated Self Bunded Tanks
Enquire For Price
Features
- True self bunded tank design with distinct Primary (Inner) and Secondary (Outer) Tanks
- Both the primary and secondary tanks can be independently integrity tested.
- The interstitial space is filled with a lightweight fireproofing material providing a Fire Resistance Level of 240 / 240 / 240
- UL2085 Listed
- UL142 / ULCS601 Designed and Approved
- AS1940-2017 Designed and Approved
- AS1692 Designed and Approved
- Size Range from 1100L through to 110,000L
- Vehicle impact protection
- Ballistic Protection
- Built-in leak detection tube
- Integrated Galvanised Step and Platform for Dipping the Tank
- Available in our unique BOX format for smaller tanks and our CONTAINERISED format in 10FT / 20FT and 40FT footprint CSC plated designs.
Installation Benefits
- Either Diesel or Petrol can be stored indoors when using a GO Fire Rated Self Bunded Tank. REF AS1940-2017 Clause 5.6.2 (c) page 64
- Separation Distances are reduced when using a GO Self Bunded Fire Rated Tank. Note as follows an excerpt from AS1940-2017 Clause 5.9.4 (d) page 73:
- To on-site and off-site protected places, the distances given in Clause 5.7 may be halved.
- To boundaries and public places - 2m.
- To any security fence - 1m.
- When storing Petrol (or indeed Diesel) a dispenser may be mounted on the tank provided it is suitable for use in the hazardous area around the tank. Refer AS1940-2017 Clause 5.9.4 d (iv) page 73
GO Fire Rated Self Bunded Tanks
Overview
GO Industrial designs, manufactures and markets a comprehensive range of Fire Rated (Vaulted) Self Bunded Tanks approved to AS1940-2017 Section 5.9.4 and UL2085 listed. The GO Fire Rated Self Bunded Tank design features a Fire Resistance Level (FRL) of 240 / 240 / 240.
- True self bunded tank design with distinct Primary (Inner) and Secondary (Outer) Tanks
- Both the primary and secondary tanks can be independently integrity tested.
- The interstitial space is filled with a lightweight fireproofing material providing a Fire Resistance Level of 240 / 240 / 240
- UL2085 Listed
- UL142 / ULCS601 Designed and Approved
- AS1940-2017 Designed and Approved
- AS1692 Designed and Approved
- Size Range from 1100L through to 110,000L
- Vehicle impact protection
- Ballistic Protection
- Built-in leak detection tube
- Integrated Galvanised Step and Platform for Dipping the Tank
- Available in our unique BOX format for smaller tanks and our CONTAINERISED format in 10FT / 20FT and 40FT footprint CSC plated designs.
- Either Diesel or Petrol can be stored indoors when using a GO Fire Rated Self Bunded Tank. REF AS1940-2017 Clause 5.6.2 (c) page 64
- Separation Distances are reduced when using a GO Self Bunded Fire Rated Tank. Note as follows an excerpt from AS1940-2017 Clause 5.9.4 (d) page 73:
- To on-site and off-site protected places, the distances given in Clause 5.7 may be halved.
- To boundaries and public places - 2m.
- To any security fence - 1m.
- When storing Petrol (or indeed Diesel) a dispenser may be mounted on the tank provided it is suitable for use in the hazardous area around the tank. Refer AS1940-2017 Clause 5.9.4 d (iv) page 73
Specifications
Code |
Size (L) |
SFL (L) |
L (mm) |
W (mm) |
H (mm) |
Weight (KG) |
FR-1 | 1100 | 1000 | 2095 | 1040 | 1550 | 1326 |
FR-2 | 2170 | 2000 | 2199 | 1667 | 1500 | 2145 |
FR-3 | 3276 | 3000 | 2200 | 1753 | 1500 | 2922 |
FR-5 | 5290 | 5000 | 2723 | 2200 | 1530 | 4445 |
FR-10LP | 10700 | 10000 | 5221 | 2200 | 1500 | 7482 |
FR-10 | 11000 | 10000 | 3950 | 2250 | 2499 | 8672 |
FR-25 | 25465 | 24190 | 6000 | 2438 | 2896 | 11046 |
FR-50 | 52255 | 49640 | 12000 | 2438 | 2896 | 24364 |